Improving the Availability of the Onitsha-New Haven 330kv Transmission Line Availability Using Adaptive PMU-Based Insulation Defect Detector

This thesis is aimed at improving the availability of the New Haven-Onitsha 330kV transmission line by
using an adaptive PMU based insulation defect detecting and location scheme. The exposed nature of
overhead power lines makes overhead power transmission lines very vulnerable to various kinds of faults.
Insulation-related faults contribute reasonably to the number of faults experienced in overhead
transmission lines. These faults cause outages in the network and reduce the availability of the
transmission lines. Poor transmission line availability means long and frequent outages which imply that
industrial and domestic consumers will have to run standby generators for longer times to sustain
production and power-dependent domestic activities. The availability of the test transmission line was
also evaluated over three years (2018 to 2020). Outage data obtained from TCN regional office Enugu
was used for the evaluation. The performance of the proposed technique in enhancing line availability
and reducing forced outage duration in the test transmission line was evaluated against the result of this
characterization. Having established in the literature that insulation defect in transmission lines is
characterized by the presence of partial discharge current pulse; a model of a three capacitor-based
partial discharge current pulse generator was used to inject partial discharge current pulse into the test
network in a controlled manner. A PMU based insulation defect detecting system was then modeled in
Simulink to detect the insulation defect that will be introduced into the network. An ANN model that will
make the PMU based insulation defect detection scheme intelligent was created, trained, and converted
into a Simulink model. Developed models were then connected and simulated to determine the
performance of the adaptive insulation defect detection system in detecting and locating insulation
defects in the test transmission line. The impact of the use of an adaptive insulation defect detection
system in preventing insulation-related faults and improving line availability (and reducing forced outage
duration) was evaluated against the values obtained without the adaptive insulation defect detection
system connected. Simulation results revealed that the proposed technique improved transmission line
availability by 2.05% with respect to the network without the adaptive PMU based insulation defect
detection scheme. It was concluded that an adaptive PMU based insulation defect detection scheme was
effective in detecting and locating insulation defects in High Voltage transmission lines. It was also
concluded that the adaptive detection scheme improved transmission line availability of the test network
relative to the transmission line without the adaptive insulation defect detection scheme


Subscribe to access this work and thousands more
Overall Rating

0

5 Star
(0)
4 Star
(0)
3 Star
(0)
2 Star
(0)
1 Star
(0)
APA

Hubs, H. (2022). Improving the Availability of the Onitsha-New Haven 330kv Transmission Line Availability Using Adaptive PMU-Based Insulation Defect Detector. Afribary. Retrieved from https://afribary.com/works/creative-accounting-and-performance-of-deposit-money-banks-in-nigeria

MLA 8th

Hubs, Hkay "Improving the Availability of the Onitsha-New Haven 330kv Transmission Line Availability Using Adaptive PMU-Based Insulation Defect Detector" Afribary. Afribary, 25 Apr. 2022, https://afribary.com/works/creative-accounting-and-performance-of-deposit-money-banks-in-nigeria. Accessed 16 Apr. 2024.

MLA7

Hubs, Hkay . "Improving the Availability of the Onitsha-New Haven 330kv Transmission Line Availability Using Adaptive PMU-Based Insulation Defect Detector". Afribary, Afribary, 25 Apr. 2022. Web. 16 Apr. 2024. < https://afribary.com/works/creative-accounting-and-performance-of-deposit-money-banks-in-nigeria >.

Chicago

Hubs, Hkay . "Improving the Availability of the Onitsha-New Haven 330kv Transmission Line Availability Using Adaptive PMU-Based Insulation Defect Detector" Afribary (2022). Accessed April 16, 2024. https://afribary.com/works/creative-accounting-and-performance-of-deposit-money-banks-in-nigeria